Permit Number: T10CM01334
Parcel: 11301146Y

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01334
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2010 STEVE SHIELDS ZONING REVIEW Approved
05/17/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide listed and labeled fire dampers for protection of ducts and penetrations of fire resistive walls. Reference: Sections 607.3, and 607.5.2, IMC 2006.
2. Clarify the location of the exhaust fans for the restrooms.
05/17/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical: Wiring for exit or em lighting in receiving or storage area to comply with 2005 NEC,700.12.F.4.

Ray T Majuta
City of Tuc, PDSD,
5/17/10
520-837-4988
05/17/2010 ROBERT SHERRY WATER REVIEW Approved
05/17/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. NEED PREVIOUS APPROVED SITE PLAN
2. MINIMUM FONT SIZE FOR BOTH UPPER AND LOWER CASE IS 3/32". PLEASE CAHNGE ALL LETTERING TO THIS STANDARD AND RESUBMIT
3. NEED FIR RATED SEPARATION BETWEEN SALES AND RECEIVING, REFERENCE TABLE 508.2, NON SPRINKLERED
05/17/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
05/17/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Clarify the description of the water heater drain noted in the plumbing fixture schedule.
3. The trap and trap arm for a lavatory may not be increased more than one size larger than the minimum trap size shown in Table 7-3. Reference: Section 1003.3, UPC 2006.
05/17/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

Need fire separation redeiving to store.
05/17/2010 RONALD BROWN ADA REVIEW Passed
05/17/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/17/2010 RONALD BROWN ZONING HC REVIEW Denied REFERENCE BUILDING COMMENTS
05/25/2010 CPIERCE1 WWM REVIEW Needs Review