Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01334
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/17/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
05/17/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide listed and labeled fire dampers for protection of ducts and penetrations of fire resistive walls. Reference: Sections 607.3, and 607.5.2, IMC 2006. 2. Clarify the location of the exhaust fans for the restrooms. |
05/17/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical: Wiring for exit or em lighting in receiving or storage area to comply with 2005 NEC,700.12.F.4. Ray T Majuta City of Tuc, PDSD, 5/17/10 520-837-4988 |
05/17/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/17/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NEED PREVIOUS APPROVED SITE PLAN 2. MINIMUM FONT SIZE FOR BOTH UPPER AND LOWER CASE IS 3/32". PLEASE CAHNGE ALL LETTERING TO THIS STANDARD AND RESUBMIT 3. NEED FIR RATED SEPARATION BETWEEN SALES AND RECEIVING, REFERENCE TABLE 508.2, NON SPRINKLERED |
05/17/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
05/17/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006. 2. Clarify the description of the water heater drain noted in the plumbing fixture schedule. 3. The trap and trap arm for a lavatory may not be increased more than one size larger than the minimum trap size shown in Table 7-3. Reference: Section 1003.3, UPC 2006. |
05/17/2010 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Need fire separation redeiving to store. |
05/17/2010 | RONALD BROWN | ADA | REVIEW | Passed | |
05/17/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/17/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | REFERENCE BUILDING COMMENTS |
05/25/2010 | CPIERCE1 | WWM | REVIEW | Needs Review |