Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01324
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/30/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A2.1; REVISION TO DOOR AT RESTROOM 12: WITH THE DOOR SWING CHANGED INTO THE HALLWAY, THE ISSUE OF DOOR ENCROACHMENT INTO THE PATH OF EGRESS TRAVEL WILL NOT ALLOW THIS LAYOUT AND SHOULD BE REVIEWED (IBC SECTION 1005.2). 2. SHEET A2.1; DOOR SWING AT RESTROOM 12: THE DOOR COULD SWING INTO THE RESTROOM IF A 30" X 48" CLEAR SPACE (PER ANSI SECTION 305) IS AVAILABLE FOR A WHEELCHAIR IN THE RESTROOM WHILE OPENING THE DOOR. THAT WAS THE REASON FOR REQUESTING AN ENLARGED RESTROOM PLAN (PREVIOUS COMMENT 1). IF THERE IS 48" AVAILABLE FROM THE INSIDE FINISH FACE OF THE NORTH WALL IN THE RESTROOM TO THE DOOR OPENING, THE SPACE WOULD MEET THAT REQUIREMENT (THERE IS 30" AVAILABLE FROM THE INSIDE FINISH FACE OF THE WEST WALL IN THE RESTROOM TO THE WATER CLOSET). PROVIDE THOSE DIMENSIONS ON THE PLAN. 3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 06/30/2010 | ERIC NEWCOMB | HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 07/07/2010 | DROBEY1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/07/2010 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/07/2010 | DROBEY1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/07/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |