Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01323
Parcel: 117160110

Address:
17 E TOOLE AV

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T10CM01323
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PER TABLE 2902.1 OF THE 2006 IBC AND SECTION 2902.2, SEPARATE FACILITIES ARE REQUIRED FOR MALE AND FEMALE OCCUPANTS. ONE DRINKING FOUNTAIN IS REQUIRED, AND ONE SERVICE SINK IS REQUIRED.
2. THIS BUILDING HAS BEEN CLASSIFIED AS A DANGEROUS BUILDING BY THE CITY OF TUCSON. PROVIDE SIGNED AND SEALED DOCUMENTATION BY A LICENSED STRUCTURAL ENGINEER, STATING THAT THEY HAVE INSPECTED THE EXISTING BUILDING CONDITIONS, AND THEY DEEM IT IS SAFE TO OCCUPY. AN ALTERNATIVE WOULD BE FOR THAT ENGINEER TO PREPARE PLANS, DETAILS, AND CALCULATIONS AS TO HOW ANY HAZARDOUS CONDITIONS WILL BE CORRECTED.
3. SHEET X1; GENERAL BUILDING SUMMARY: THE TOTAL BUILDING AREA IS LISTED AS 35,992 SF. VERIFY THAT NUMBER.
4. SHEET A1; REFERENCE FLOOR PLANS: HAS THE BASEMENT BEEN INCLUDED IN THE BUILDING SQUARE FOOTAGE? OCCUPANCY LOAD IS BASED ONLY ON THE GROUND LEVEL FLOOR PLAN.
5. THIS IS A CHANGE OF USE FROM THE LAST ESTABLISHED USE OF THIS BUILDING. SHOW THE ACCESSIBLE ROUTE FROM THE STREET INTO AND THROUGH THE SPACE PER IBC SECTION 3409.
6. WILL THIS BUILDING BE REVIEWED AS A SEPARATED FACILITY? VERIFY.
05/13/2010 ANY WWM REVIEW Active
05/13/2010 ERIC NEWCOMB ADA REVIEW Passed
05/13/2010 ANY WATER REVIEW Active
05/13/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/13/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
05/14/2010 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Denied THIS BUILDING IS KNOWN TO THE CITY OF TUCSON AS BEING LISTED AS A "DANGEROUS BUILDING". PLEASE PROVIDE SEALED DOCUMENTATION THAT ANY EXISTING PLUMBING, MECHANICAL AND/OR ELCTRICAL SYSTEMS MEET MINIMUM CODE REQUIREMENTS.

PROVIDE COMPLETE PLANS SHOWING THIS SPACE MEETS ALL REQUIREMENTS FOR THIS CHANGE OF OCCUPANCY.
05/14/2010 TERRY STEVENS ZONING REVIEW Approved
05/14/2010 JASON GREEN ENGINEERING REVIEW Needs Review FUP required. Either Substantial Improvement review or provide an ELCERT showing conformance with the FFE requriements.
05/14/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied THIS BUILDING IS KNOWN TO THE CITY OF TUCSON AS BEING LISTED AS A "DANGEROUS BUILDING". PLEASE PROVIDE SEALED DOCUMENTATION THAT ANY EXISTING PLUMBING, MECHANICAL AND/OR ELCTRICAL SYSTEMS MEET MINIMUM CODE REQUIREMENTS.

PROVIDE COMPLETE PLANS SHOWING THIS SPACE MEETS ALL REQUIREMENTS FOR THIS CHANGE OF OCCUPANCY.
05/14/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

Swinging doors are required front and rear for Group B with 33 occupants. Front and rear exits are required because of the depth of the building has a common path of travel greater than 75 feet on the unsprinklered first floor.

The basement is required to be fire sprinklered.

Address the Dangerous Building issue.

Explain the openings in the basement to other basements. Is the whole structure the same fire area? What is the total area?
05/14/2010 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Denied THIS BUILDING IS KNOWN TO THE CITY OF TUCSON AS BEING LISTED AS A "DANGEROUS BUILDING". PLEASE PROVIDE SEALED DOCUMENTATION THAT ANY EXISTING PLUMBING, MECHANICAL AND/OR ELCTRICAL SYSTEMS MEET MINIMUM CODE REQUIREMENTS.

PROVIDE COMPLETE PLANS SHOWING THIS SPACE MEETS ALL REQUIREMENTS FOR THIS CHANGE OF OCCUPANCY.