Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01309
Parcel: 117042890

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T10CM01309
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/22/2010 RONALD BROWN ZONING HC REVIEW Approved
07/28/2010 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Mr Heads
T10CM01309
Building Plan (2nd Review)

TRANSMITTAL DATE: July 28, 2010

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan.. Please submit two copies of the approved and stamped site plan with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t10cm01309.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
08/02/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; an economizer alone may not allow the heat pump to handle 100% outside air. Verify with the heat pump manufacturer that the existing A/C unit will be able to supply essentially 100% outside air to the space on a design day (cooling). Reference: Section 304.1, IMC 2006.
08/02/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the size of the indirect waste piping that exceeds 5'-0" in length to be the minimum size allowed per Table 7-5, UPC 2006. Reference: Sections 703.0 and 803.0, UPC 2006.
2. Provide a full-sized vent from downstream of the backwater valve to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area.
08/02/2010 ROBERT SHERRY WATER REVIEW Approved
08/18/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2010 SUE REEVES OUT TO CUSTOMER Completed
08/19/2010 SUE REEVES REJECT SHELF Completed