Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01302
Parcel: 12810082B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01302
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project: T10CM01302
5340 E Broadway

Electrical plans denied for the following:

1. Sheet E-1, new circuit for canopy lights on circuit LPB-26, load not included in panel schedule.
2. Sheet E-2, circuit LPA-36 not in panel schedule.
3.Sheet E-3, circuit AC- 1,3,5 not in panel schedule.
4.Sheet E-3, circuit AC-2 not in panel schedule.
5.Sheet E-5, the loads in Panel LPD have changed for some reason,(could you explain why), and the new loads have not been transposed to Panel AC, the loads in Panel AC need to be updated as well as the total loads.
6. What has happened to the mech-interlock on sheet E-5 ?
Will the interlock now be handled by the hood pnl , if so please include on plan.



Ray T Majuta
PDSD, City of Tucson
Elect Pln Ck
8/2/10
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/21/2010 DELMA ROBEY OUT TO CUSTOMER Completed