Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: MODULAR BUILDINGS
Permit Number - T10CM01284
Review Name: MODULAR BUILDINGS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/11/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/11/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 05/11/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 05/11/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Passed | PREMANUFACTURED OFFICES ARE STATE REGULATED |
| 05/11/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/11/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 05/11/2010 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 05/11/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 05/11/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/11/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |