Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01282
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide waste and vent isometrics for the new work. Reference: Section 103.2.3, UPC 2006. 2. Provide a floor drain in the kitchen. Reference: Sections 411.2.2 and 704.3, UPC 2006. 3. Show that the indirect waste piping from the sanitizing compartment of the 3-compartment sink complies with the requirements of Section 803.0, UPC 2006 with respect to length (i.e. does it have a trap?). 4. Provide a detail of the installation of the 3-compartment sink and hydromechanical grease interceptor. |
| 05/21/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the construction of the Type I hoods; detail 6/M2 appears to show a hood with make up air being supplied directly to the hood cavity which would adversely effect the amount of make up air being supplied to the building. Reference: Section 507.13, IMC 2006. |
| 05/24/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 306 N Alvernon Wy, T10CM01282 Lodge on The Desert, Fire Damage The Electrical Plans provided require additional information in order to approve , the information requested is as follows; 1. The previous permits obtained for this address have not provided information on total load calculations, the latest permit for Temporary Electrical Repair due to fire did not provide any information. Would you provide a more concise load total on service and calculation to verify safe amount on service.The service appears to be old and added on to over time. 2. Provide notation on electrical indicating identification of high leg on service and panels per 2005 NEC 110-15,230-56,408.3(E),409.102, for contractors and inspectors benefit. Ray T Majuta, Elect Pln Review, PDSD, City of Tucson 5/25/10 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/03/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 06/03/2010 | SUE REEVES | REJECT SHELF | Completed |