Permit Number: T10CM01278
Parcel: 13204271A

Address:
3285 E 44TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01278
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2010 MARTIN BROWN FIRE REVIEW Approved
05/13/2010 GERRY KOZIOL WWM REVIEW Passed
05/19/2010 RONALD BROWN ZONING HC REVIEW Denied Reference building folder for comments
05/19/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Because the new addition effects the occupancy load, exiting and toilet facilities, a new Cerificate of Occupancy must be issued for the entire building. In order to properly evaluate the effects of the new addition as to allowable size, added occupants for exiting and toilet facilities a general code review analysis must be conducted for the entire building. Please provide a floor plan of the total building and a new completed code analysis check list for same.
2. Minimum font size is 3/32" (upper and/or lower case) as per P&DSD standards. Please review sheets G-1, F-1 of 3, F-2 of 3, F-3 of 3, E1 of 11 through E11 of 11, and SD1 of 9 through SD9 of 9, resize all fonts below this standard and resubmit.
3. Please correct reference symbols 1 and 2 on detail 1A-2.
4. Please provide special inspection certificates as summerized on sheet S1.0.
5. Please provide structural details and calculations for the evaporative cooler supports on the side of the metal building.
6. Please provide structural details and calculations for the roof top mounted evaporative coolers including existing structural framing evaluation of additional load.
7.
05/21/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/07/2010 ROBERT SHERRY WATER REVIEW Denied Provide a site plan showing the location of the reduced pressure backflow assembly on the drawing and indicate the size of the assembly. Reference: COT Backflow Prevention Ordinance, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
06/07/2010 TERRY STEVENS ZONING REVIEW Denied The proposed addition is located within the R-1 zoned property. Zoning cannot further review or approve until the rezoning of the R-1 portion of this property has been completed.
06/07/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide energy code compliance calculations for the building envelope. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
06/07/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/10/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
06/10/2010 GERARDO BONILLA REJECT SHELF Completed