Permit Number: T10CM01263
Parcel: 13403036A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T10CM01263
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2010 MARTIN BROWN FIRE REVIEW Approved
06/03/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM01263
8727 E 22ND ST

. Electrical plans denied for the following:

1. Must provide location to Main SES Electrical Service on plan, also provide location of Utility Transformer.
2. Must provide 2005 City of Tucson Outdoor Lighting Calculation, Ord # 10035.

Ray T Majuta
Elect Pln Ck, PDSD, City of Tucson,
6/3/10
520-837-4988
06/04/2010 GBONILL1 WWM REVIEW Needs Review