Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01245
Parcel: 111050770

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01245
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2010 ROBERT SHERRY WATER REVIEW Passed
10/13/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the waste and vent isometric to coordinate with the plumbing plan. Reference: Section 103.2.3, UPC 2006.
2. If the model number of the proposed water fountain is correctly written, Elkay does not include it in its list of products. If the model number is actually EMABFDL, the specified drinking fountain does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006.
3. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatories. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
4. The specified water closets require a minimum pressure greater than the 15-PSI used in the water pipe sizing calculations. Revise calculations as necessary. Reference: Section 608.1, UPC 2006.
5. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
6. Revise the scupper calculation on sheet A4.0 to show compliance with the requirements of Section 1101.11.2.1, UPC 2006 and to coordinate with the scupper size shown on detail 8/A5.0. If the scupper for the existing roof is being installed at this time, correct the size per Section 1101.11.2.1, UPC 2006.
10/13/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the new addition complies with the energy code requirements for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Clarify the ventilation calculations; if you are using ASHRAE Standard 62.1-2004 for education, classroom (ages 5 - 8), State that. To complete the calculation, you must include the zone air distribution effectiveness from Table 6-2 (in this case, ceiling supply/ceiling return = 0.8).
3. Verify that the existing A/C unit has the heating capacity to supply the required outside air and still maintain the room temperature at 68 degrees Fahrenheit on a design day (32 degrees Fahrenheit). Reference: Section 309.1, IMC 2006.
4. Clarify where detail 1/M1.0 occurs. Reference: Section 106.3.1, IMC 2006.
10/18/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
10/18/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Toilet 104 is not accessible compliant as required by 2006 IBC, Section 1109.
2. Please provide a Hi/Low drinking fountain as required by Section 1109.5 and ICC (ANSI 117.1), Section 602.
3. As per Table 1004.1.1, the occupancy load for classroom is 1/20 and when calculated with the building square footage of 1,323 square feet, the occupant load is 66.
a. Please file an appeal with the Building Official for any reduction in the code required occupant load.
SHEET A1.2
4. Generic accessible code compliant details are not acceptable. Please provide large scale interior toilet elevations of both toilets and include all dimensions and accessories for accessible code compliance.
5. Detail Enlarged Plan 103:
a. Please show both toilets.
b. Both toilets are to be 100% accessible
c. Please show all accessible dimensions required and accessories.
6. With a code occupancy load of 66, panic hardware is required for all exit doors as per Section 1008.1.9.
7. The structural calculations are very confusing. Please provide a framing and a foundation key plan and provide references to all calculated structural framing and foundation elements of the structural design.
8. Please provide structural connection details and structural calculations for all new roof top mounted HVAC units.
9. Please provide structural connection details and structural calculations for the wall mounted water heater.
10. because no Special Inspections were listed by the structural engineer as per the 2006 IBC, Section 1704.1.1., Inspections were added in the Conditions Menu of this Permit application. Please have the structural engineer review this list and submit the appropriate completed special Inspection Certifications. If he feels that this list should be adjusted, please submit changes in writing,.
END OF REVIEW
10/18/2010 RONALD BROWN ZONING HC REVIEW Denied Please reference the Building Folder for comments
10/25/2010 BIANCA RAMIREZ ENGINEERING REVIEW Denied Cannot approve building plan until site plan has been approved.
10/26/2010 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Outer Limits School - Classroom Addition
T10CM01245
Building Plan (1st Review)

TRANSMITTAL DATE: October 26, 2010

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan.. Please submit two copies of the approved and stamped site plan with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t10cm01245.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
11/03/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/04/2010 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/22/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
11/22/2010 SUE REEVES REJECT SHELF Completed