Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM01244
Parcel: 11707270A

Address:
555 E 18TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01244
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2010 ROBERT SHERRY WATER REVIEW Approved
05/13/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
05/13/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/13/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/13/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/14/2010 GERRY KOZIOL WWM REVIEW Passed