Permit Number: T10CM01244
Parcel: 11707270A

Address:
555 E 18TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01244
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
05/06/2010 JASON GREEN ENGINEERING REVIEW Approved
05/06/2010 RONALD BROWN ADA REVIEW Passed
05/06/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. FIX ALL RAMPS AND STAIRS TO BE COMPLIANT WITH CODE, HANDRAILS, SLOPES AND ETC.
2. SHOW ALL HANDRAILS ON FLOOR PLAN
05/06/2010 RONALD BROWN ZONING HC REVIEW Denied 1. FIX ALL ACCESSIBLE ENTRYS TO COMPLY WITH ANSI 117.1.
2. CONFIRM DISTANCE FROM WALL TO CENTER LINE OF WATER CLOSETS
05/06/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/07/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the scope of mechanical work to be done.
05/07/2010 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
05/07/2010 ROBERT SHERRY WATER REVIEW Denied Confirm the existance of a reduced pressure backflow preventer for the water service to the building.
05/07/2010 MARTIN BROWN FIRE REVIEW Approved
05/07/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The minimum font size is 3/32"
05/13/2010 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2010 DELMA ROBEY OUT TO CUSTOMER Completed