Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01243
Parcel: 110113620

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T10CM01243
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2010 SREEVES1 ADA REVIEW Passed
05/17/2010 DAVE MANN FIRE REVIEW Approved
05/20/2010 GERRY KOZIOL WWM REVIEW Denied NEED WASTEWATER 5TH FLOOR CREDIT EVALUATION FOR EXSISTING 2 TOILETS & 2 LAVS PER DRAWING
05/21/2010 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/27/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT; GENERAL: ALL LETTERING MUST BE A MINIMUM OF 3/32" IN HEIGHT PER CITY OF TUCSON REQUIREMENTS (SHEETS a1.1/ACCUREX SHEET/a2.0).
2. PREVIOUS COMMENT; GENERAL: REPRINT SHEETS THAT HAVE THE TOP AND/OR RIGHT SIDE CUT OFF (SHEETS a2.0/a2.?/a4.0/a5.0).
3. PREVIOUS COMMENT; GENERAL: SHEETS a5.0/a9.0/a9.2 REQUIRE A PROFESSIONAL STAMP, SIGNATURE, AND DATE ON THE DRAWING.
4. PREVIOUS COMMENT; GENERAL: PROVIDE ENLARGED PLAN OF THE RESTROOMS. PROVIDE WALL ELEVATIONS INDICATING COMPLIANCE WITH THE ICC/ANSI A117.1-2003.
5. PREVIOUS COMMENT; SHEET a2.0; FLOOR PLAN KEY NOTES: NOTE 20 REFERENCES STRUCTURAL SHEETS NOT INCLUDED IN THIS SET. VERIFY.
6. PREVIOUS COMMENT; SHEET a2.0; GENERAL NOTES: NOTE 19 INDICATES THERE IS STRUCTURAL FRAMING ON A SHELL THAT NEEDS TO BE VERIFIED. CLARIFY.
7. PREVIOUS COMMENT; GENERAL: NEW MECHANICAL LOADS ON THE EXISTING ROOF NEED TO BE VERIFIED BY A STRUCTURAL ENGINEER THAT THE LOADS DO NOT EXCEED THE STRUCTURES CAPACITY.
8. PREVIOUS COMMENT; GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/01/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. PREVIOUS COMMENT: SEE BUILDING COMMENTS.
06/07/2010 RICK MYERS PLUMBING-COMMERCIAL REVIEW Approved 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments.
06/08/2010 RMYERS1 WATER REVIEW Approved
06/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
2. Provide sufficient information and details to show that the design and termination of the water heater vent complies with sections 510.6 and 511.0, UPC 2006.
06/15/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied 1) NEC 210.8(B) GFCI PLUG RECEPTACLES REQUIRED IN COMMERCIAL KITCHENS.

2) NEC 110.3 PP-E3.O THE CALCULATED FAULT CURRENT AT PANEL B IS SHOWN TO BE 24,000 AMPS BUT KEYNOTE 2 TO SAME PANEL IS CALLING FOR 22K AIC BREAKERS. PLEASE CLARIFY.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2010 ANY REJECT SHELF RECEIVED