Permit Number: T10CM01243
Parcel: 110113620

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01243
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2010 STEVE SHIELDS ZONING REVIEW Approved
05/06/2010 LOREN MAKUS ENGINEERING REVIEW Approved
05/06/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: ALL LETTERING MUST BE A MINIMUM OF 3/32" IN HEIGHT PER CITY OF TUCSON REQUIREMENTS (SHEETS a1.1/ACCUREX SHEET/a2.0).
2. GENERAL: REPRINT SHEETS THAT HAVE THE TOP AND/OR RIGHT SIDE CUT OFF (SHEETS a2.0/a2.?/a4.0/a5.0).
3. GENERAL: SHEETS a5.0/a9.0/a9.2 REQUIRE A PROFESSIONAL STAMP, SIGNATURE, AND DATE ON THE DRAWING.
4. GENERAL: PROVIDE ENLARGED PLAN OF THE RESTROOMS. PROVIDE WALL ELEVATIONS INDICATING COMPLIANCE WITH THE ICC/ANSI A117.1-2003.
5. SHEET a2.0; FLOOR PLAN KEY NOTES: NOTE 20 REFERENCES STRUCTURAL SHEETS NOT INCLUDED IN THIS SET. VERIFY.
6. SHEET a2.0; GENERAL NOTES: NOTE 19 INDICATES THERE IS STRUCTURAL FRAMING ON A SHELL THAT NEEDS TO BE VERIFIED. CLARIFY.
7. GENERAL: NEW MECHANICAL LOADS ON THE EXISTING ROOF NEED TO BE VERIFIED BY A STRUCTURAL ENGINEER THAT THE LOADS DO NOT EXCEED THE STRUCTURES CAPACITY.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/06/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
05/14/2010 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review
05/14/2010 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/14/2010 CPIERCE1 WATER REVIEW Needs Review
05/14/2010 CPIERCE1 FIRE REVIEW Needs Review
05/14/2010 CPIERCE1 WWM REVIEW Needs Review
05/14/2010 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review