Permit Number: T10CM01234
Parcel: 116170060

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01234
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. 2006 IBC REQUIRES SEPARATE RESTROOM FACILITIES FOR ASSEMBLY OCCUPANCIES PER SECTION 2902.2. VERIFY.
2. IF THE PATIO AREA SERVES DRINK AND/OR FOOD, THE SPACE MUST BE INCLUDED IN THE OCCUPANT LOAD CALCULATION.
05/05/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/05/2010 ERIC NEWCOMB ADA REVIEW Passed
05/05/2010 ROBERT SHERRY WATER REVIEW Approved
05/05/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/05/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.
2. Provide an upper terminal cleanout for the dishwasher. Reference: section 707.4, UPC 2006.
05/05/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
05/06/2010 STEVE SHIELDS ZONING REVIEW Approved
05/06/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
05/06/2010 DAVE MANN FIRE REVIEW Approved
05/07/2010 GBONILL1 WWM REVIEW Needs Review
05/07/2010 GBONILL1 ENGINEERING REVIEW Needs Review