Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01223
Parcel: 12611153A

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T10CM01223
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1; EAST ELEVATION: SHOW AN ENLARGED DETAIL OF HOW THE NEW MASONRY PARAPET WALL IS CONNECTED TO THE EXISTING WALL. STRUCTURAL CALCULATIONS ARE REQUIRED FOR THIS WALL AND CONNECTION DESIGN.
2. SHEET A1; EAST ELEVATION: THE SECTION CUT AT THE LOW BUILDING INDICATES 6/A2. THERE IS NO SECTION 6. CLARIFY.
3. SHEET A1; EAST ELEVATION: THE SECTION CUT AT THE HIGH BUILDING INDICATES 4/A2. VERIFY.
4. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR ALL THE NEW FRAMING AND THEIR CONNECTIONS TO THE EXISTING STRUCTURE.
05/05/2010 JASON GREEN ENGINEERING REVIEW Approved
05/05/2010 MARTIN BROWN FIRE REVIEW Approved
05/05/2010 DAVID RIVERA ZONING REVIEW Approved