Permit Number: T10CM01201
Parcel: 12217001A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01201
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2010 GERRY KOZIOL WWM REVIEW Passed
05/13/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/13/2010 ROBERT SHERRY WATER REVIEW Approved
05/13/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The mechanical plan indicates that 90 CFM of supply air will be introduced into the restroom but only 75 CFM will be exhausted. Revise the balancing data and provide a sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
05/19/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A.1; FLOOR PLAN: PER THE 2006 IBC, SECTION 1010.6.3, THE LENGTH OF THE LANDING SHALL BE 60" MINIMUM. REVISE DRAWING.
2. SHEET A.1; FLOOR PLAN: PER THE 2006 IBC, SECTION 1012.5, HANDRAILS SHALL EXTEND A MINIMUM OF 12" BEYOND THE TOP AND BOTTOM OF RAMPS. REVISE DRAWING.
3. SHEET A.1; FLOOR PLAN: PER THE 2006 IBC, SECTION 1012, PROVIDE SPECIFICATIONS ON THE PLAN FOR HANDRAIL REQUIREMENTS.
4. SHEET A.1; FLOOR PLAN: IS THE EXISTING TOILET ACCESSIBLE? EXPLAIN.
5. SHEET A.1; FLOOR PLAN: PER THE 2006 IBC, TABLE 2902.1, A BUSINESS OCCUPANCY REQUIRES A DRINKING FOUNTAIN. PROVIDE.
6. SHEET A.1; FLOOR PLAN: PROVIDE A DETAIL AT THE SOUTHWEST CORNER OF THE BUILDING, INDICATING HOW THE NEW STUD WALL IS CONNECTED TO THE EXISTING CMU WALL.
7. SHEET A.1; FLOOR PLAN: PROVIDE A DETAIL AT THE BUILDING ENTRY DOOR, INDICATING HOW THE NEW STUD WALL IS CONNECTED TO THE EXISTING WALL.
8. SHEET A.1; SECTION 1: THE DETAIL AT THE TOP OF THE WALL IS DENOTED AS 2.S.1. REVISE.
9. SHEET A.1; SECTION 1: THE DETAIL AT THE BOTTOM OF THE WALL HAS BEEN CHANGED BY HAND TO A/S.2. REVISE.
10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/20/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
05/27/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved