Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01201
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2010 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 05/13/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/13/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/13/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The mechanical plan indicates that 90 CFM of supply air will be introduced into the restroom but only 75 CFM will be exhausted. Revise the balancing data and provide a sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. |
| 05/19/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A.1; FLOOR PLAN: PER THE 2006 IBC, SECTION 1010.6.3, THE LENGTH OF THE LANDING SHALL BE 60" MINIMUM. REVISE DRAWING. 2. SHEET A.1; FLOOR PLAN: PER THE 2006 IBC, SECTION 1012.5, HANDRAILS SHALL EXTEND A MINIMUM OF 12" BEYOND THE TOP AND BOTTOM OF RAMPS. REVISE DRAWING. 3. SHEET A.1; FLOOR PLAN: PER THE 2006 IBC, SECTION 1012, PROVIDE SPECIFICATIONS ON THE PLAN FOR HANDRAIL REQUIREMENTS. 4. SHEET A.1; FLOOR PLAN: IS THE EXISTING TOILET ACCESSIBLE? EXPLAIN. 5. SHEET A.1; FLOOR PLAN: PER THE 2006 IBC, TABLE 2902.1, A BUSINESS OCCUPANCY REQUIRES A DRINKING FOUNTAIN. PROVIDE. 6. SHEET A.1; FLOOR PLAN: PROVIDE A DETAIL AT THE SOUTHWEST CORNER OF THE BUILDING, INDICATING HOW THE NEW STUD WALL IS CONNECTED TO THE EXISTING CMU WALL. 7. SHEET A.1; FLOOR PLAN: PROVIDE A DETAIL AT THE BUILDING ENTRY DOOR, INDICATING HOW THE NEW STUD WALL IS CONNECTED TO THE EXISTING WALL. 8. SHEET A.1; SECTION 1: THE DETAIL AT THE TOP OF THE WALL IS DENOTED AS 2.S.1. REVISE. 9. SHEET A.1; SECTION 1: THE DETAIL AT THE BOTTOM OF THE WALL HAS BEEN CHANGED BY HAND TO A/S.2. REVISE. 10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/20/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 05/27/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |