Permit Number: T10CM01190
Parcel: 117170090

Address:
118 S 5TH AV #01

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01190
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2010 DAVE MANN FIRE REVIEW Approved
06/08/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. At Detail 1/5.0, please provide fire sealant requirements for all penitrations through fire rated wall.
2. At Detail 1/A2.0, a two hour rated enclosure is referenced by key note W-04. Is this necessary?
3. Please clarify the existing wall construction fire ratings between both the South adjacent building and the Julian Drew Building and show wall sections on drawings.
4. Please provide a water heater support detail and structural calculations.

END OF REVIEW
06/08/2010 RONALD BROWN ZONING HC REVIEW Denied Reference Building Folder Comments
06/09/2010 TERRY STEVENS ZONING REVIEW Denied CAnnot approve until the site plan has been approved.
06/15/2010 BIANCA RAMIREZ ENGINEERING REVIEW Denied Site plan comments must be addressed and approved prior to the approval of any building plans.

Bianca Ramirez
06/17/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. The code analysis provided by the architect lists the 2006 Uniform Plumbing Code for this activity but the mechanical specifications and the plumbing sheets are using the 2006 International Plumbing Code. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC.
06/17/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/17/2010 ROBERT SHERRY WATER REVIEW Passed
06/17/2010 GERRY KOZIOL WWM REVIEW Denied needs capacity letter- Kurt Stemm- 740-6607
needs 5th floor credit evaluation
needs to show location/method of connection to public sewer.
06/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/25/2010 CPIERCE1 OUT TO CUSTOMER Completed
06/25/2010 SUE REEVES REJECT SHELF Completed