Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01189
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/03/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | CANNOT APPROVE BUILDING UNTIL SITE PLAN IS APPROVED |
| 06/07/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | 1. Please provide a hi/low drinking fountain in the office shell as required by ICC (ANSI 117.1), Section 602.4. |
| 06/08/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. At Detail 1/5.0, please provide fire sealant requirements for all penitrations through fire rated wall. 2. At Detail 1/A2.0, a two hour rated enclosure is referenced by key note W-04. Is this necessary? 3. Please provide a hi/low drinking fountain. END OF REVIEW |
| 06/09/2010 | TERRY STEVENS | ZONING | REVIEW | Denied | Cannot approve until the site plan has been approved. |
| 06/17/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/17/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. The code analysis provided by the architect lists the 2006 Uniform Plumbing Code for this activity but the mechanical specifications and the plumbing sheets are using the 2006 International Plumbing Code. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC. |
| 06/17/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/17/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | needs capacity letter- Kurt Stemm- 740-6607 needs 5th floor credit evaluation needs to show location/method of connection to public sewer. |
| 06/23/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/25/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 06/25/2010 | SUE REEVES | REJECT SHELF | Completed |