Permit Number: T10CM01173
Parcel: 122140080

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01173
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2010 TERRY STEVENS ZONING REVIEW Approved
04/29/2010 PAUL MACHADO ENGINEERING REVIEW Approved
04/29/2010 RONALD BROWN ADA REVIEW Passed
04/29/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/29/2010 RONALD BROWN ZONING HC REVIEW Approved
04/29/2010 DAVE MANN FIRE REVIEW Approved
04/29/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/03/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the total amount of ventilation air introduced by the HVAC unit is sufficient to supply the air required for transfer to the restrooms and for ventilation of the other spaces being served by the HVAC unit. Reference: Sections 403.2.2 and 403.3.3, IMC 2006.
2. Revise the size of the grease ducts to provide a minimum velocity of 1500 feet per minute. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson.
3. Provide adequate make up air for the kitchen exhaust hood. Reference: Section 508.1 IMC 2006.
4. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
05/03/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/03/2010 ROBERT SHERRY WATER REVIEW Approved
05/04/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM01173 , 1200 N Country Club
Office TI



1. Circuits A2-14 and A2-14----one of these should be A2-16.
2. Two walk in coolers listed in pantry are not listed in Mechanical Plan.
3. Provide a note on plan indicating that Panel A will be a listed feed through Panel.



Ray T Majuta
5/3/10
PDSD, Tucson
Elect Plan Ck
520-837-4988
05/05/2010 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2010 DELMA ROBEY OUT TO CUSTOMER Completed