Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01169
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T10CM01169
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2010 DAVE MANN FIRE REVIEW Approved
06/02/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. CONCERNING THE LETTERING SIZE (COMMENT 6) IT IS CLEAR THE UPPER CASE LETTERING MEETS THE MINIMUM 3/32" HEIGHT, BUT ALL LOWER CASE LETTERING IS LESS THAN THAT. THIS REVIEW HAS BEEN APPROVED. THIS NOTE IS FOR FUTURE REFERENCE ONLY.
06/03/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
06/04/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Comment not resolved; indicate on the drawings which appliance needs which type of backflow protection device. Appliances (e.g. espresso makers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
06/04/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. The minimum required ventilation is to be based on Table 403.3, IMC 2006 or an approved engineering analysis of the specific occupancy type. Reference: Sections 105.2 and 403.3, IMC 2006.
06/10/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/23/2010 CPIERCE1 OUT TO CUSTOMER Completed
06/23/2010 SUE REEVES REJECT SHELF Completed