Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/28/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
04/28/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
04/28/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | ENGINEER HAS INDICATED EXISTING 1" C --4-#6 W/1 #10 GND FROM 60A/60AF METERED DISCONNECT AT RISER DIAGRAM PP E3.0. PLEASE CLARIFY HOW THIS IS CONSISTENT WITH OR HOW TRANSITION WILL BE MADE TO SIMILAR NOTE SAME DETAIL AT RELOCATED TRANSFORMER INDICATING 3/4" C --3 #6 W/1 #10 GND. |
04/28/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/28/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A6.2; DETAIL 4c: PROVIDE VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 604.5.1. |
04/28/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
04/28/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
04/28/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/28/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
04/28/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENT. |
04/30/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
05/05/2010 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/05/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |