Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01089
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/21/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/21/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
04/21/2010 | RONALD BROWN | ADA | REVIEW | Passed | |
04/21/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Minimum lettering font size is 3/32" upper and lower case. 2. Recalculate occupancy load. 3. Rework exits if occupancy load is more than 50. 4. There is another comment; provide structural detailing and calculations for the new roof mounted HVAC unit and for the type 1 exhaust hood support. 5. At detail 1/M1, please to define what material is non combustable wall and what is the finish of that wall behind the hood and oven/range? END OF REVIEW |
04/21/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/28/2010 | GBONILL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
04/28/2010 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
04/28/2010 | GBONILL1 | WATER | REVIEW | Needs Review | |
04/28/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/28/2010 | GBONILL1 | WWM | REVIEW | Needs Review | |
04/28/2010 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
04/28/2010 | RONALD BROWN | ZONING HC | REVIEW | Needs Review |