Permit Number: T10CM01089
Parcel: 11707208A

Address:
758 S STONE AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01089
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
04/21/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
04/21/2010 RONALD BROWN ADA REVIEW Passed
04/21/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Minimum lettering font size is 3/32" upper and lower case.
2. Recalculate occupancy load.
3. Rework exits if occupancy load is more than 50.
4. There is another comment; provide structural detailing and calculations for the new roof mounted HVAC unit and for the type 1 exhaust hood support.
5. At detail 1/M1, please to define what material is non combustable wall and what is the finish of that wall behind the hood and oven/range?
END OF REVIEW
04/21/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/28/2010 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
04/28/2010 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review
04/28/2010 GBONILL1 WATER REVIEW Needs Review
04/28/2010 MARTIN BROWN FIRE REVIEW Approved
04/28/2010 GBONILL1 WWM REVIEW Needs Review
04/28/2010 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/28/2010 RONALD BROWN ZONING HC REVIEW Needs Review