Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01051
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 04/23/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/06/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006. 2. Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings; indicate the size and location of the reduced pressure backflow prevention assembly for this building. Reference: COT Backflow Prevention Ordinance, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
| 05/06/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/06/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fan so that that all of the air supplied to the restroom will be exhausted (i.e. if the fan is switched with the restroom light, the air supplied to the room when the light is off will not be exhausted). Reference: Section 403.2.1 (4), IMC 2006. |
| 05/10/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROJECT: T10CM01051, 8886 E Tanque Verde, Electrical denied see comments for activity # T10CM01049. Ray T Majuta, 5/10/10 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/12/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 05/12/2010 | SUE REEVES | REJECT SHELF | Completed |