Permit Number: T10CM01050
Parcel: 114540640

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01050
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2010 DAVE MANN FIRE REVIEW Approved
04/23/2010 GERRY KOZIOL WWM REVIEW Approved
05/05/2010 ROBERT SHERRY WATER REVIEW Denied 1. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006.
2. Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings; indicate the size and location of the reduced pressure backflow prevention assembly for this building. Reference: COT Backflow Prevention Ordinance, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
05/05/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
05/05/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the size of the common condensate drain in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson.
2. Revise the sequence of operation for the restroom exhaust fans so that that all of the air supplied to the restrooms will be exhausted (i.e. if the fan is switched with the restroom light, the air supplied to the room when the light is off will not be exhausted). Reference: Section 403.2.1 (4), IMC 2006.
3. Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2006.
05/10/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM1050


See denied comments for activity # T10CM01049

Ray T Majuta,5/10/10

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2010 DELMA ROBEY OUT TO CUSTOMER Completed
05/12/2010 SUE REEVES REJECT SHELF Completed