Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01035
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Section 608.7, UPC 2006 requires the installation of a vacuum relief valve (not a vacuum breaker) in storage-type water heaters located above the hot water fixture outlets. The installation of the vacuum relief valve shall be in accordance with the manufacturer's installation instructions (in this case, there are to be no valves between the vacuum relief and the storage tank). |
| 06/21/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | Clarify the demand; a demand of 2900 cubic feet per second (29 CCFS) sounds like a river. |
| 06/21/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used. In addition, the areas and occupany types used in the calculations must be coordinated with the architectural design. |
| 06/28/2010 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 06/28/2010 | CPIERCE1 | WWM | REVIEW | Needs Review |