Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01035
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 04/16/2010 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/19/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/20/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations demonstrating adequate ventilation. Reference: Section 401.2, IMC 2006. |
| 04/20/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/20/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Show that the water service to the building is protected with a backflow preventer. 2. What is the size of the existing water meter and what is the demand on the meter. |
| 04/20/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 04/20/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/20/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 05/12/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a floor drain in the kitchen. Reference: Sections 411.2.2 and 704.3, UPC 2006. 2. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006. 3. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006. 4. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006. 5. Verify the presence of an integral flow control device for the hydromechanical grease interceptor. |
| 06/21/2010 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 06/21/2010 | CPIERCE1 | FIRE | REVIEW | Needs Review |