Permit Number: T10CM01024
Parcel: 10714376H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01024
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Structural calculations and detail for overstressed beam from new HVAC unit needs to be provided on the drawings.
2. The East HVAC unit has not been addressed has to it's effect on the over stressd glue lam beam. Please clarify.
05/19/2010 STEVE SHIELDS ZONING REVIEW Approved
05/19/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The occupant load used to calculate the required ventilation for a fast food restaurant is 100 people per 1000 square feet, not 70 people per 1000 square feet. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2006 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2006.
05/19/2010 MARTIN BROWN FIRE REVIEW Approved
05/19/2010 ROBERT SHERRY WATER REVIEW Approved
05/19/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/04/2010 CPIERCE1 ENGINEERING REVIEW Needs Review
06/04/2010 CPIERCE1 WWM REVIEW Needs Review
06/04/2010 CPIERCE1 ZONING HC REVIEW Completed
06/04/2010 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review