Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM00997
Parcel: 117170010

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00997
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2010 STEVE SHIELDS ZONING REVIEW Approved
04/14/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Verify that the location of the water heater next to the relocated fan coil will not block maintenance access to the fan coil.
04/14/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/14/2010 ROBERT SHERRY WATER REVIEW Approved
04/14/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE CALCULATIONS FOR ADEQUACY OF FRAMING TO SUPPORT FAN COIL AND HOT WATER HEATER.
2. DRINKING FOUNTAIN NEEDS TO BE HIGH/LOW OR SINGLE POINT OF USE FOR ACCESSIBILITY.
3. ANY INTERIOR WALL OVER 6' IN HEIGHT MUST BE DESIGNED/BRACED TO MEET IBC SECTION 1607.13 LATERAL LOAD REQUIREMENTS.
4. PROVIDE SITE PLAN.
04/14/2010 JASON GREEN ENGINEERING REVIEW Approved
04/14/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a vacuum relief for the water heater.
04/14/2010 MARTIN BROWN FIRE REVIEW Approved
04/14/2010 ERIC NEWCOMB ADA REVIEW Passed
04/14/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/14/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
04/19/2010 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2010 DELMA ROBEY OUT TO CUSTOMER Completed