Review Details: RESUBMITTAL

Permit Number - T10CM00990
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2010 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 11-09-10
Activity: T10CM00990 2nd Review
Address: 2926 E 19th St
Applicant: Alex Valadez

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings and one set of the first submission for reference. All corrections and revisions shall be made on original tracings or finished reproducible set. Pencil and/or white out on final prints will not be acceptable. To expedite review, please cloud the originally submitted set with red ink and limit clouding on final set. Ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

2. Provide an emergency escape/rescue opening serving each sleeping room in the building, R310.
Existing bedroom being converted to a den needs to meet the egress criteria.

STRUCTURAL / FRAMING PLAN:
3. Justify the proposed beam size for the specified load on the front porch.
Beam specified is not large enough to accommodate the proposed load.

ELEVATIONS:
4. Clarify all window sizes and locations consistent with floor plan.
Floor plan shows three small windows on the west side of the addition and the elevation show one in that place.

ELECTRICAL PLAN:
5. Laundry rooms receptacles require at least one 20-amp circuit that shall serve no other outlets, E3603.3, 3801.8.
20 amp laundry circuit may not share lighting or exhaust fans.

If you have any questions please contact: