Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10CM00990
Parcel: 129060180

Address:
2926 E 19TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T10CM00990
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2010 GERRY KOZIOL WWM REVIEW Approved
09/16/2010 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 9-21-10
Activity: T10CM00990
Address: 2926 E 19th St
Applicant: Alex Valadez

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings and one set of the first submission for reference. All corrections and revisions shall be made on original tracings or finished reproducible set. Pencil and/or white out on final prints will not be acceptable. To expedite review, please cloud the originally submitted set with red ink and limit clouding on final set. Ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related new or revised sheets of plans including details and calculations in accordance with the rules of the State Board of Technical Registration.

3. Provide an emergency escape/rescue opening serving each sleeping room in the building, R310.

STRUCTURAL / FRAMING PLAN:
4. Specify rafter length on the front porch consistent with the appropriate span allowance for the proposed material, R802.1.
5. Justify the proposed beam size for the specified load on the front porch.

ELEVATIONS:
6. Clarify all window sizes and locations consistent with floor plan.

SECTIONS - DETAILS:
7. Ceiling gypsum board must be either 5/8" or ½" sag resistant when applied to ceilings framed at 24" o/c, IRC table R702.3.5 footnote d.
8. Specify finished floor elevation above grade with appropriate exterior wall covering height above grade, R319.1.4, R404.1.6, R703.6.2.1.
9. Include dropped ceiling on cross section details and specify support/connection to wall.

PLUMBING PLAN:
10. Specify water conservation requirements: Water closets = 1.6 gallons per flush, Sinks = 2.2 gpm, Showerheads = 2.5 gpm, P2903.2.
11. Shower and tub/shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
12. Provide note requiring that water hammer arrestor be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, IRC P2903.5.
13.

MECHANICAL PLAN:
14. Gas appliances shall comply with ARIZONA STATE PLUMBING CODE combustion air requirements or Chapter 17, 2006 IRC. Show compliance for all appliances. Confined spaces require a minimum of two 100 SQ. IN. openings, M1702.2.

ELECTRICAL PLAN:
15. Laundry rooms receptacles require at least one 20-amp circuit that shall serve no other outlets, E3603.3, 3801.8.
16. Provide electrical load calculations for determining the service panel size, E3502.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2010 DELMA ROBEY OUT TO CUSTOMER Completed
09/30/2010 SUE REEVES REJECT SHELF Completed