Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM00989
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00989
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vacuum relief for the storage-type water heater located above the fixture outlets. Reference: Section 608.7, UPC 2006.
2. Provide an end of run cleanout at the mop sink, SS1. Reference: Section 707.4, UPC 2006.
3. Provide protection of the trap seals for all floor drains subject to infrequent use. Reference: Sections 1007.0 and 1007.1, UPC 2006, as amended by the City of Tucson.
04/14/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006.
2. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.
3. Revise the sequence of operation for the restroom exhaust fans (i.e. switched with lights) so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (3), IMC 2006.
4. Smoke detectors shall be located upstream of any outside air connections. Reference: Section 606.2.1, IMC 2006.
04/14/2010 MARTIN BROWN FIRE REVIEW Approved
04/15/2010 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Plans Denied for the following:

1. Revise sequence of operation for restroom exhaust fan. See mechanical review comment #3. Needs to operate when air being supplied to restroom.

2. Revise sheet E2 to clarify installation of New 45KVA xfmr or relocating existing 30KVA xfmr. 30KVA xfmr not of sufficent size to supply calculated loads.

3. Provide disconnecting means for water heater. Refrence 2005 NEC 422.31(B).

Rich Jiroudek
Electric Plns Exmn

Final Status

Task End Date Reviewer's Name Type of Review Description
04/27/2010 CPIERCE1 OUT TO CUSTOMER Completed
04/27/2010 SUE REEVES REJECT SHELF Completed