Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00989
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/13/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 04/13/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006. 2. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006. 3. Revise the sequence of operation for the restroom exhaust fans (i.e. switched with lights) so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (3), IMC 2006. 4. Smoke detectors shall be located upstream of any outside air connections. Reference: Section 606.2.1, IMC 2006. |
| 04/13/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/13/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/13/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/13/2010 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 04/13/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a vacuum relief for the storage-type water heater located above the fixture outlets. Reference: Section 608.7, UPC 2006. 2. Provide an end of run cleanout at the mop sink, SS1. Reference: Section 707.4, UPC 2006. 3. Provide protection of the trap seals for all floor drains subject to infrequent use. Reference: Sections 1007.0 and 1007.1, UPC 2006, as amended by the City of Tucson. |
| 04/13/2010 | CAGUILA1 | FIRE | REVIEW | Needs Review | |
| 04/13/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 04/13/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/13/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 04/14/2010 | GERRY KOZIOL | WWM | REVIEW | Approved |