Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM00982
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/12/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S500 (FOUNDATION PLAN); CALCULATIONS SHEET E27: THE EAST AND WEST WALL FOOTINGS ARE DENOTED AS F1 IN THE CALCULATIONS (2'-4"WX10"TH), BUT AS F4 (1'-4"WX24"TH) ON THE DRAWINGS. CLARIFY. 2. SHEET S504; DETAIL 311: GIVE THE VERTICAL AND HORIZONTAL DIMENSIONS OF THE 1/4" BENT PLATE. 3. SHEET S504; DETAIL 312: GIVE THE VERTICAL AND HORIZONTAL DIMENSIONS OF THE 1/4" BENT PLATE. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/14/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |