Permit Number: T10CM00982
Parcel: 10712225A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00982
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S500 (FOUNDATION PLAN); CALCULATIONS SHEET E27: THE EAST AND WEST WALL FOOTINGS ARE DENOTED AS F1 IN THE CALCULATIONS (2'-4"WX10"TH), BUT AS F4 (1'-4"WX24"TH) ON THE DRAWINGS. CLARIFY.
2. SHEET S504; DETAIL 311: GIVE THE VERTICAL AND HORIZONTAL DIMENSIONS OF THE 1/4" BENT PLATE.
3. SHEET S504; DETAIL 312: GIVE THE VERTICAL AND HORIZONTAL DIMENSIONS OF THE 1/4" BENT PLATE.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2010 SUE REEVES OUT TO CUSTOMER Completed