Permit Number: T10CM00968
Parcel: 124091120

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T10CM00968
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2010 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T10CM00967 & 968
1611 East 10th Street units 1 & 2
Addition to existing SFR (Unit 1) and new SFR (Unit 2)


TRANSMITTAL: June 22, 2010


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


The site is located in the R-2 Zone (LUC Section 2.3.5). The Development Designator is "K" (LUC Section 2.3.5.A.2) and the Perimeter Yard Indicator is BB (LUC Sections 3.2.3.1.C and 3.2.6.4).

Clearly depict the existing structure within the property line as discussed at the counter.

Include all the proposed vehicle use area in the coverage calculation. Also state on the plan that four parking spaces are required and four are provided (2.25 for the three bedroom unit and 2.0 for the two bedroom unit). (See LUC Section 3.3.4 Multifamily.)

Please remove all references to any "Future" structure that are not be permitted at this time.

Provide dimensions on the elevation plans from ground to highest point of each wall on Sheet T1.0 for setback information (LUC Section 3.2.6.4).

Please be aware that further comments may be necessary relative to additional information provided with subsequent submittals.
06/23/2010 GERRY KOZIOL WWM REVIEW Denied CONNECTING TO EXSISTING ON-SITE PRIVATE SEWER
NEED CAPASITY EVALUATION BY PCRWRD- KURT STEMM-740-6607- 3RD FLOOR
07/13/2010 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T10CM00968 Unit #1 Addition

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007 and the 2006 UPC with amendments on 7/10/2007. For initial construction: Effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation are required for all new SFR and duplex plans. Show the code references on the plans. Amendments to adopted codes are at the City web-site http://www.tucsonaz.gov: Planning, Building, & Business; under the Building topic; Building Ordinances and Codes; Building Codes

FOUNDATION PLANS:

1. Show compliance with termite treatment, R320 as amended.

FLOOR PLANS:

1. Clarify overtyped notation on the Demo Plan sheet A1.1, R106.1.1.

STRUCTURAL PLANS:

1. Clarify if B6 will support existing roof loads. Show the load bearing structure of the existing Bedroom roof framing for verifying the load carrying capacity of B6 sheet S1.1, R301.1.

SECTIONS - DETAILS:

1. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.

MECHANICAL PLANS:

1. Show a means of supplying combustion air to the water heater within the confined space, G2407.5.

ELECTRICAL PLANS:

1. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3602.2.
2. Protect bedroom outlets including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3802.12.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Show the "R" values of insulation and the maximum "U" factors of the windows and doors on the plans, N1101.2.
2. Both standard and high density R-30 batt insulation requires a space greater than provided with (J1) 2" x 6" framing. Identify the product that provides the intended value, or provide an appropriate ceiling cavity space.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review