Permit Number: T10CM00952
Parcel: 127071210

Address:
5220 E 7TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T10CM00952
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2010 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL


FROM: Terry Stevens, Lead Planner

PROJECT:
T10CM00952
5220 E. 7th St.
Carport

TRANSMITTAL: April 9, 2010


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO).


This site is located in the R-1 Zone (LUC Section 2.3.4.2.A.1). The Development Designator is "G" (LUC Section 3.2.3.1.B) and the Perimeter Yard Indicator is AA (LUC Section 3.2.6.4).

The required street perimeter yard setback is the greater of twenty (20) feet or 1 ½ times the height of the structure's wall facing the property line (LUC Section 3.2.6.5.A).

The required setback for interior lot lines is the greater of six (6) feet or two-thirds (2/3) the height of the structure's wall facing the property line (LUC Section 3.2.6.4).

The required setback is twenty (20) feet to the north property line and the proposed setback is eleven (11) foot nine (9) inches.

The required setback is six (6) feet to the west property line and the proposed setback is two (2) feet.

DDO required.
04/09/2010 TERRY STEVENS NPPO REVIEW Passed
06/04/2010 CPIERCE1 BUILDING-RESIDENTIAL REVIEW Needs Review
06/04/2010 CPIERCE1 WWM REVIEW Needs Review
06/04/2010 CPIERCE1 ENGINEERING REVIEW Needs Review