Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00935
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET C-1; SUMMARY OF GOVERNING REGULATIONS TABLE: UPDATE THIS TABLE TO CURRENT CODES USED BY THE CITY OF TUCSON. |
| 04/20/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 3/32-inch (all upper case). Reference: Section 106.1.1, IBC 2006. 2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006. 3. Clarify the status of heat pumps HP-1, 2, 3, & 4: new or existing. 4. State the minimum R-value for the duct insulation. |
| 04/20/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM00935 Previously you had not submitted a one line diagram, the new one indicates a new service, two new panels and a 45 KVA transformer.The new panels show existing loads. This is confusing, the ground to the secondary of the transformer should be a # 6 cu. The notes on electrical sheets that indicate for new circuits if new fixtures require, determination should be made on these plans not left up to contractor. Location of transformer ? If service is new as indicated provide available fault current up to panels. The existing service on load totals shows only 20 amps, was there no load on this service other than the 20 amps ? Ray T Majuta PDSD, City of Tucson Elect Plan Ck 4/20/10 Ray.Majuta@tucsonaz.gov |