Permit Number: T10CM00935
Parcel: 14029037B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00935
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET C-1; SUMMARY OF GOVERNING REGULATIONS TABLE: UPDATE THIS TABLE TO CURRENT CODES USED BY THE CITY OF TUCSON.
04/20/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 3/32-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006.
3. Clarify the status of heat pumps HP-1, 2, 3, & 4: new or existing.
4. State the minimum R-value for the duct insulation.
04/20/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM00935


Previously you had not submitted a one line diagram, the new one indicates a new service, two new panels and a 45 KVA transformer.The new panels show existing loads. This is confusing, the ground to the secondary of the transformer should be a # 6 cu.
The notes on electrical sheets that indicate for new circuits if new fixtures require, determination should be made on these plans not left up to contractor.
Location of transformer ?
If service is new as indicated provide available fault current up to panels.
The existing service on load totals shows only 20 amps, was there no load on this service other than the 20 amps ?

Ray T Majuta
PDSD, City of Tucson
Elect Plan Ck
4/20/10