| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 04/08/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a design for the modifications to the mechanical system. Show the ductwork, location of the A/C units, and the air balancing data. 2. Clarify the space above the ceiling and indicate the minimum R-value for the duct insulation. |
| 04/08/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 04/08/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/08/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET C-1: INDICATE OCCUPANCY LOAD IN THE CODE ANALYSIS. 2. GENERAL: ALL LETTERING MUST BE A MINIMUM OF 3/32" HEIGHT. 3. SHEET A-2; DETAIL 4: PER THE IBC SECTION 1607.13., INTERIOR PARTITIONS MUST HAVE ADEQUATE STRENGTH TO RESIST LATERAL LOADS. PROVIDE BRACING AT THE TOP OF THE WALL, INDICATING BRACE SIZE, SPACING, AND CONNECTION TO THE EXISTING STRUCTURE ABOVE AND TO THE TOP OF THE WALL. 4. SHEET A-2; FLOOR PLAN: PROVIDE STRUCTURAL CALCULATIONS FOR THE PARTITION SUPPORT BEAM, COLUMNS, AND EXISTING SLAB ADEQUACY TO SUPPORT THOSE NEW LOADS. CALCULATIONS MUST BE BY A LICENSED PROFESSIONAL. |
| 04/08/2010 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 04/08/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/08/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 04/08/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/08/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 04/08/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/20/2010 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |