Review Details: COMMERCIAL TI

Permit Number - T10CM00935
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2010 TERRY STEVENS ZONING REVIEW Approved
04/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a design for the modifications to the mechanical system. Show the ductwork, location of the A/C units, and the air balancing data.
2. Clarify the space above the ceiling and indicate the minimum R-value for the duct insulation.
04/08/2010 ERIC NEWCOMB ADA REVIEW Passed
04/08/2010 ROBERT SHERRY WATER REVIEW Approved
04/08/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET C-1: INDICATE OCCUPANCY LOAD IN THE CODE ANALYSIS.
2. GENERAL: ALL LETTERING MUST BE A MINIMUM OF 3/32" HEIGHT.
3. SHEET A-2; DETAIL 4: PER THE IBC SECTION 1607.13., INTERIOR PARTITIONS MUST HAVE ADEQUATE STRENGTH TO RESIST LATERAL LOADS. PROVIDE BRACING AT THE TOP OF THE WALL, INDICATING BRACE SIZE, SPACING, AND CONNECTION TO THE EXISTING STRUCTURE ABOVE AND TO THE TOP OF THE WALL.
4. SHEET A-2; FLOOR PLAN: PROVIDE STRUCTURAL CALCULATIONS FOR THE PARTITION SUPPORT BEAM, COLUMNS, AND EXISTING SLAB ADEQUACY TO SUPPORT THOSE NEW LOADS. CALCULATIONS MUST BE BY A LICENSED PROFESSIONAL.
04/08/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
04/08/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/08/2010 PAUL MACHADO ENGINEERING REVIEW Approved
04/08/2010 MARTIN BROWN FIRE REVIEW Approved
04/08/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
04/08/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/20/2010 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review