Permit Number: T10CM00924
Parcel: 13609024R

Review Status: Completed

Review Details: SITE

Permit Number - T10CM00924
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2010 RBROWN1 ADA REVIEW Passed Not a COT owned/operated property
04/08/2010 MARTIN BROWN FIRE REVIEW Approved
04/09/2010 ANDREW CONNOR NPPO REVIEW Approved
04/09/2010 ANDREW CONNOR LANDSCAPE REVIEW Approved Ensure that all Engineering comments and concerns are addressed prior NPP / Landscape approval stamp.
04/09/2010 DAVID RIVERA ZONING REVIEW Approved
04/13/2010 LOREN MAKUS ENGINEERING REVIEW Approved
04/14/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/14/2010 RONALD BROWN ZONING HC REVIEW Denied 1. It appears that three accessible passenger loading zones are designed for this project. Only one is required and it may be any of the three shown on sheet shown on sheet C2. It needs to comply with 2006 IBC, ICC (ANSI) 117.1, Section 503 which requires a separate 5' wide by 20 long accessible aisle adjacent to the vehicle parking space.
2. Please clarify if traffic flow is one way or two way. If it is two way, this may effect required parking space at suggested passenger loading zone. Reference zoning comments.
3. The other two areas indicated as an accessible loading areas should be deleted and retain a raised curb at these two areas. The curb provides a vision impared person sufficient warning that a hazardious vehicle area is beyond.
END OF REVIEW