| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/13/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SEE BUILDING COMMENTS FOR ACTIVITY NUMBER T10CM00713. |
| 04/20/2010 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 04/20/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the size of the gutter to comply with the requirements of Section 1106.3, UPC 2006. Refer also to Section 1106.4, UPC 2006. |
| 04/20/2010 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | Plan will be approved once the site plan is approved. |
| 04/20/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations using the correct climate zone (Pima County < 4,000 feet) and the correct code (2006 IECC). (Note that the Mechanical Compliance Certificate shown on sheet M2.1 uses the 2009 IECC and is for Phoenix, AZ.) Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. Provide the cooling and heating load calculations used to justify the size of the heat pumps. Reference: Section 503.2.1, IECC 2006. |
| 04/20/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/21/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/23/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |