Permit Number: T10CM00880
Parcel: 11706166A

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T10CM00880
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Denied for following:
1.Tap conductors to new panels are fed of 1200 amp disconnect , 2005 NEC 250.122, requires a 3/0 cu ground
2. Panel schedules to have discription of circuit use, vsuch as room number.

Ray T Majuta
4/05/10
04/05/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/05/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/06/2010 DAVE MANN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/04/2010 GERARDO BONILLA OUT TO CUSTOMER Completed