Permit Number: T10CM00839
Parcel: 11901076A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM00839
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not addressed. Revise the waste and vent diagram on sheet P.1 to eliminate the wet venting of P-3; it has 3 drainage fixture units and cannot be the upper fixture on a wet vent. Reference: Section 908.1, UPC 2006.
07/15/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/21/2010 SUE REEVES OUT TO CUSTOMER Completed