Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00839
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a complete mechanical design for the installation of the Type I hood. The design shall include all information needed to show that the installation complies with the requirementas of Sections 506, 507, and 508, IMC 2006; shop drawings from the hood manufacturer are not an adequate substitute for sealed plans from an Arizona registrant. |
| 04/09/2010 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A.1; FLOOR PLAN (NOTE 17): THE NOTE REFERS TO STRUCTURAL FOR A LINTEL DETAIL. NO STRUCTURAL IS INCLUDED IN THIS SET. 2. SHEET TS1; PROJECT DATA: THE OCCUPANCY GROUP IS DEFINED AS M. REVISE TO RESTAURANT. PROVIDE OCCUPANY LOAD AND BUILDING SQUARE FOOTAGE ON THE SHEET. 3. SHEET A.1; DETAIL 3: THE NOTE TO BRACE THE WALL TO THE STRUCTURE ABOVE PER IBC SECTION 1621.2.7. WHAT IS THIS CODE SECTION? 4. SHEET A.1; DETAIL 3: PROVIDE NOTES ON THE CONNECTION OF THE 3-5/8" STUDS TO ROOF JOISTS. PROVIDE BRACE SIZES, SPACING, AND CONNECTION OF BRACE AT THE TOP AND BOTTOM. |
| 04/12/2010 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Sheet TS1 1. The occupancy group is not M, it is A-2. Please see IFC Section 202. 2. The fire code is the 2006 IFC. 3. Provide a Code Review Checklist with the ocupant load. Sheet A.1 1. The doors do not have the separation required by IFC 1015.2.1. Sheet K.1 1. The fryer must be under the hood by at least 6 inches. See IFC Section 904.11. |
| 04/15/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | need addressing review per Pima Co Addressing |
| 04/21/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006. 2. Revise the site drawing to show the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006. |
| 04/22/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide fixture descriptions for all plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006. 2. Revise the fixture units used to calculate the total water demand and determine pipe sizes to use "assembly" occupancy. Reference: Section 610.1, UPC 2006. 3. Determine the size of the waste water pipes using the fixture units shown in Table 7-3. Use "assembly" occupancy where appropriate and also correct the fixture units used for the 3-compartment sinks, the mop basin, and the floor sinks. Reference: Section 703.1, UPC 2006. 4. Keynote 18 on sheet P.1 calls for the indirect waste from the sanitizing compartment of the 3-compartment sink at the bar and the prep sink (P-7) to terminate at a floor sink. Keynote 24 similarly calls for the indirect waste from the dishwasher to terminate at a floor sink. The closest floor sinks appear to be between 5 and 15 feet from the fixtures and the dishwasher therefore, show the size and routing of the indirect waste lines, along with their required traps. Reference: Section 803.0, UPC 2006. 5. The plumbing floor plan shows a floor sink located directly east of the Type I hood in the kitchen; what fixtures or appliances are draining to it? Reference: Section 103.2.3, UPC 2006. 6. The minimum size of an indirect waste line from a plumbing fixture shall be in accordance with Table 7-5, UPC 2006. Reference: Section 803.0, UPC 2006. 7. Resize the proposed grease interceptor per Section 1014.3.6, UPC 2006 using the revised waste fixture units, including the dishwashing machine. 8. Size natural gas pipe per Section 1217.1, UPC 2006 or provide calculations demonstrating conformance to Section 1217.3, UPC 2006. |
| 04/30/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 05/05/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/07/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |