Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T10CM00839
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/31/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/31/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/31/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 03/31/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 03/31/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A.1; FLOOR PLAN (NOTE 17): THE NOTE REFERS TO STRUCTURAL FOR A LINTEL DETAIL. NO STRUCTURAL IS INCLUDED IN THIS SET. 2. SHEET TS1; PROJECT DATA: THE OCCUPANCY GROUP IS DEFINED AS M. REVISE TO RESTAURANT. PROVIDE OCCUPANY LOAD AND BUILDING SQUARE FOOTAGE ON THE SHEET. 3. SHEET A.1; DETAIL 3: THE NOTE TO BRACE THE WALL TO THE STRUCTURE ABOVE PER IBC SECTION 1621.2.7. WHAT IS THIS CODE SECTION? 4. SHEET A.1; DETAIL 3: PROVIDE NOTES ON THE CONNECTION OF THE 3-5/8" STUDS TO ROOF JOISTS. PROVIDE BRACE SIZES, SPACING, AND CONNECTION OF BRACE AT THE TOP AND BOTTOM. |
| 03/31/2010 | ENEWCOM1 | ADA | REVIEW | Passed | |
| 04/09/2010 | GBONILL1 | FIRE | REVIEW | Needs Review |