Permit Number: T10CM00792
Parcel: 124050600

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00792
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 5; DETAIL 4: PROVIDE INFORMATION/CUT SHEETS CONCERNING UNISTRUT SUPPORTS AND HOW THEY FASTEN TO THE HOOD.
05/24/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a complete design for the new natural gas service. Show the loads of all gas-fired equipment (e.g. burners, oven, griddle, and fryer) and the materials of construction.
05/24/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/24/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the dimensions of the hood, grease duct, the equipment under the hood, and the operation of the hood comply with the requirements of sections 506 and 507, IMC 2006.
2. Show how the makeup air is to be introduced into the kitchen. Reference section 508, IMC 2006.
3. Provide information to show that the hood is listed per the manufacturer.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/16/2010 DELMA ROBEY OUT TO CUSTOMER Completed