Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM00792
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/24/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET 5; DETAIL 4: PROVIDE INFORMATION/CUT SHEETS CONCERNING UNISTRUT SUPPORTS AND HOW THEY FASTEN TO THE HOOD. |
| 05/24/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a complete design for the new natural gas service. Show the loads of all gas-fired equipment (e.g. burners, oven, griddle, and fryer) and the materials of construction. |
| 05/24/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/24/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the dimensions of the hood, grease duct, the equipment under the hood, and the operation of the hood comply with the requirements of sections 506 and 507, IMC 2006. 2. Show how the makeup air is to be introduced into the kitchen. Reference section 508, IMC 2006. 3. Provide information to show that the hood is listed per the manufacturer. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/16/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |