Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM00778
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00778
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2010 DAVID RIVERA ZONING REVIEW Approved
03/26/2010 PAUL MACHADO ENGINEERING REVIEW Approved
03/26/2010 ERIC NEWCOMB ADA REVIEW Passed
03/26/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE STRUCTURAL CALCULATIONS FOR THE STOREFRONT FRAMING.
03/26/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
03/26/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/29/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 3/32-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
3. Keynote 2, sheet M1.0 calls for 1200 CFM of outside air for the existing rooftop A/C unit but the outside air calculations on sheet M2.0 call for 1450 CFM of outside air. Coordinate the ventilation requirements.
4. Materials exposed in plenums shall conform to Section 602.2.1, IMC 2006.
5. Indicate the location of the smoke detectors for RTU-1. Reference: Section 606.1, IMC 2006.
03/29/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide cleanouts sized per Section 707.11, UPC 2006.
2. The specified model of tankless water heater is not capable of limiting the water temperature to 110 F. Specify a model that is capable of limiting the water temperature to 110F
03/29/2010 ROBERT SHERRY WATER REVIEW Approved
03/29/2010 GERRY KOZIOL WWM REVIEW Approved
03/30/2010 DAVE MANN FIRE REVIEW Approved
04/01/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM00778, 5870 E Broadway Bl
TI for Guess

The electrical plans have been denied for the following:

1. Actual Fault Current values to be listed for each panel.
Sheet E0.0 Under Panelboards, #5 " actual AIC short current ratings to be verified on site." Please provide these, are required in order to approve plans for permit.
2. Some track lighting does not appear to be calculated at 150 va per every 2 feet.( NEC 2005, 220-43. B.)
3. Does load calculation for lighting include amount required for continous duty?


Ray T Majuta,
Elect Pln Ck
PDSD, City of Tucson
4/05/10
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
04/23/2010 SUE REEVES REJECT SHELF Completed