Permit Number: T10CM00777
Parcel: 106101650

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T10CM00777
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied The work shown in the construction documents- Additive Alternate 2/Administration Building, requires work to be completed in the Central Plant Building #3. Each separate building must have a separate permit. The review below is for the Central Plant Building, Building #3 and it's associated cold water piping to the new administration building.
1. Please prouide a separate plan showing both the Administration Building and the Central Plant Building.
a. Show in detail exactly where the Supply and return cold water piping enters both buildings and exactly where it is connected equipment wise.
b. Please show the exact route of the shallow tunnel and where and how it terminates at both buildings.
c. Please provide construction details and calculations of the shallow tunnel.
e. Please provide any other structural calculations for the placement of new equipment that may effect the existing structural elements.
2. Please provide a detailed code analysis data sheet providing all the required code information plus estimated evaluation.
3. Please revise the title of this construction package and Index to include Building 3 as part of the construction.
4. Please include an overall site plan of the entire Sun Tran Facilities identifying all new and existing buildings.
END OF REVIEW.
04/26/2010 RONALD BROWN ADA REVIEW Passed
04/26/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Provide the design basis for the size of the common chiller relief vent (i.e. the allowable length and the minimum internal diameter of the vent serving the two pressure relief valves or rupture disks). Reference: Sections 106.3.1 and 1101.2, IMC 2006.
04/28/2010 MARTIN BROWN FIRE REVIEW Approved
05/04/2010 LOREN MAKUS ENGINEERING REVIEW Approved
05/12/2010 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/19/2010 SUE REEVES OUT TO CUSTOMER Completed
05/19/2010 SUE REEVES REJECT SHELF Completed