Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T10CM00777
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | The work shown in the construction documents- Additive Alternate 2/Administration Building, requires work to be completed in the Central Plant Building #3. Each separate building must have a separate permit. The review below is for the Central Plant Building, Building #3 and it's associated cold water piping to the new administration building. 1. Please prouide a separate plan showing both the Administration Building and the Central Plant Building. a. Show in detail exactly where the Supply and return cold water piping enters both buildings and exactly where it is connected equipment wise. b. Please show the exact route of the shallow tunnel and where and how it terminates at both buildings. c. Please provide construction details and calculations of the shallow tunnel. e. Please provide any other structural calculations for the placement of new equipment that may effect the existing structural elements. 2. Please provide a detailed code analysis data sheet providing all the required code information plus estimated evaluation. 3. Please revise the title of this construction package and Index to include Building 3 as part of the construction. 4. Please include an overall site plan of the entire Sun Tran Facilities identifying all new and existing buildings. END OF REVIEW. |
| 04/26/2010 | RONALD BROWN | ADA | REVIEW | Passed | |
| 04/26/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Provide the design basis for the size of the common chiller relief vent (i.e. the allowable length and the minimum internal diameter of the vent serving the two pressure relief valves or rupture disks). Reference: Sections 106.3.1 and 1101.2, IMC 2006. |
| 04/28/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/04/2010 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 05/12/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/19/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 05/19/2010 | SUE REEVES | REJECT SHELF | Completed |