Permit Number: T10CM00777
Parcel: 106101650

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T10CM00777
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/15/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the addition of the new chiller to the central plant does not cause the machinery room ventilation system to no longer comply with the requirements of Section 1105, IMC 2006.
2. Provide the design basis for the size of the common chiller relief vent (i.e. the allowable length and the minimum internal diameter of the vent serving the two pressure relief valves or rupture disks). Reference: Sections 106.3.1 and 1101.2, IMC 2006.
3. Revise the termination of the chiller pressure relief vent to comply with the requirements of Section 1105.7, IMC 2006.
04/15/2010 ROBERT SHERRY WATER REVIEW Approved
04/15/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
04/19/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/21/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/21/2010 SREEVES1 ZONING HC REVIEW Passed
04/26/2010 CPIERCE1 ENGINEERING REVIEW Needs Review
04/26/2010 CPIERCE1 ZONING REVIEW Needs Review
04/26/2010 CPIERCE1 ADA REVIEW Needs Review
04/26/2010 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
04/26/2010 CPIERCE1 FIRE REVIEW Needs Review