Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T10CM00777
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/15/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
04/15/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the addition of the new chiller to the central plant does not cause the machinery room ventilation system to no longer comply with the requirements of Section 1105, IMC 2006. 2. Provide the design basis for the size of the common chiller relief vent (i.e. the allowable length and the minimum internal diameter of the vent serving the two pressure relief valves or rupture disks). Reference: Sections 106.3.1 and 1101.2, IMC 2006. 3. Revise the termination of the chiller pressure relief vent to comply with the requirements of Section 1105.7, IMC 2006. |
04/15/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/15/2010 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
04/19/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/21/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/21/2010 | SREEVES1 | ZONING HC | REVIEW | Passed | |
04/26/2010 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
04/26/2010 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
04/26/2010 | CPIERCE1 | ADA | REVIEW | Needs Review | |
04/26/2010 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
04/26/2010 | CPIERCE1 | FIRE | REVIEW | Needs Review |