Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T10CM00735
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE THE STRUCTURAL DRAWINGS OF THE EXISTING ROOF FRAMING THAT THE PV SYSTEM WILL BE SUPPORTED BY. 2. PROVIDE STRUCTURAL CALCULATIONS TO SHOW THAT THE NEW PV SYSTEM CAN BE ADEQUATELY SUPPORTED BY THE EXISTING ROOF STRUCTURE. 3. PROVIDE STRUCTURAL CALCULATIONS AND DETAILS FOR THE CONNECTION OF THE NEW PV SYSTEM TO THE EXISTING ROOF STRUCTURE. |
| 03/24/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/24/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/24/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/25/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 03/25/2010 | DAVID RIVERA | ZONING | REVIEW | Approved |